TEST SITE

Heaters

Section Code 1465 : Combination boilers and Water Jacketed Tube heaters. Low volume water content. Heat retained in water heaters will cause expansion of water after closure of draw-off taps and valves. Provision for expansion of water must be made to accommodate excess pressure within the system. Particular care is required where check valves are positioned, or loose jumper valves are thought to be upstream of the heater.

Back To Directory Sections

#2309044

Range of wall mounted combination boilers providing domestic hot water via a heat exchanger and pressurised central heating system. The products can be supplied with a rigid or flexible filling loop or keyless filling link. The flexible and rigid filling loops incorporate a flexible hose or copper pipe, isolation valve, double check valve assembly (suitable for back flow protection against fluid category 3). The keyless filling link incorporates a CAB backflow prevention device (suitable for back flow protection against fluid category 3). The products also incorporate an expansion vessel and pressure relief valve set at 3.0 bar. Maximum working pressure of primary circuit 2.5 bar. Maximum operating temperature of primary circuit 85°C Maximum working pressure of secondary circuit 8.0 bar Maximum operating temperature of secondary circuit 60°C

Section:
1465 Heaters
Section Subtitle:
Combination boilers and Water Jacketed Tube heaters. Low volume water content. Heat retained in water heaters will cause expansion of water after closure of draw-off taps and valves. Provision for expansion of water must be made to accommodate excess pressure within the system. Particular care is required where check valves are positioned, or loose jumper valves are thought to be upstream of the heater.
WRAS Approval Number:
2309044
Size:
¾” BSP (M) (primary circuit). ½” BSP (M) (secondary circuit).
Marking:
Baxi on front cover.
Installation Requirements:
R001 R140 R360
Expiry date:
30/09/2028
Model:
7796586 BAXI 624 COMBI 2 7796587 BAXI 630 COMBI 2 7796588 BAXI 636 COMBI 2 7813609 BAXI 624 COMBI LPG 2 7814304 BAXI 824 COMBI 2 7814305 BAXI 830 COMBI 2 7814306 BAXI 836 COMBI 2 7814307 BAXI 830 COMBI LPG 2 7814308 BAXI 836 COMBI LPG 2 7814309 BAXI ASSURE 524 COMBI 2 7814310 BAXI ASSURE 530 COMBI 2 7814311 BAXI ASSURE 536 COMBI 2 7814312 BAXI ASSURE 530 COMBI LPG 2

Approval Holder:
Baxi Heating UK Limited
Company Name
Baxi Heating UK Limited
Address
Brooks House, Coventry Road, Warwick
Postcode
CV34 3LL

View All Listings by this Company

Print This Approval


#2309313

‘SATK 32’ range of indirect heat interface units providing instantaneous hot water. Domestic hot water is provided via a plate heat exchanger and this circuit incorporates a flow detector, stainless-steel filter and water hammer arrestor. The primary/space heating circuit incorporates a pressure relief valve set at 2.5 bar and an expansion vessel. Maximum working pressure of the domestic hot water circuit is 10.0 bar. Maximum working pressure of the primary circuit is 16.0 bar. Maximum working pressure of the space heating circuit is 2.5 bar. Maximum operating temperature 90°C.

Non-metallic materials and components comply with BS6920 at 85°C

Section:
1465 Heaters
Section Subtitle:
Combination boilers and Water Jacketed Tube heaters. Low volume water content. Heat retained in water heaters will cause expansion of water after closure of draw-off taps and valves. Provision for expansion of water must be made to accommodate excess pressure within the system. Particular care is required where check valves are positioned, or loose jumper valves are thought to be upstream of the heater.
WRAS Approval Number:
2309313
Size:
¾” BSP (M).
Marking:
Caleffi and Caleffi logo moulded on face of unit. Caleffi, Caleffi logo, model number and technical info on data plate inside unit.
Installation Requirements:
R001 R140 R360
Expiry date:
30/09/2028
Model:
SATK32103 - Wall-mounted Indirect Heat Interface Unit for Instantaneous domestic hot water production – DHW capacity 50kW. SATK32105 - Wall-mounted Indirect Heat Interface Unit for Instantaneous domestic hot water production – DHW capacity 60kW. SATK32107 - Wall-mounted Indirect Heat Interface Unit for Instantaneous domestic hot water production – DHW capacity 75kW.

Approval Holder:
Caleffi S.p.A
Company Name
Caleffi S.p.A
Address
PLANT 2. S.R. 229 28010 Fontaneto d'Agogna (NO)
Country
Italy
Phone
+39 0322 8491
General Email
info@caleffi.com

View All Listings by this Company
Manufacturer:
Caleffi S.p.A
Company Name
Caleffi S.p.A
Address
PLANT 2. S.R. 229 28010 Fontaneto d'Agogna (NO)
Country
Italy
Phone
+39 0322 8491
General Email
info@caleffi.com

View All Listings by this Company

Print This Approval



Back To Directory Sections

Page 2 of 2

We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.