Range of wall hung, gas fired, combination boilers providing domestic hot water via a plate heat exchanger.
The primary circuit incorporates an integral expansion vessel and a pressure relief valve set at 3.0 bar.
The product is supplied with a rigid pipe filling loop, followed by a separate isolation valve. The filling loop pipe attaches to the cold water inlet valve which incorporates a double check valve assembly (verified by test, suitable for backflow protection against Fluid Category 3) on the branch to the filling loop.
The primary circuit includes an isolation valve on the flow and return and is also supplied with two loose 22mm compression isolation valves and a filter.
Maximum working pressure of the primary circuit is 2.5 bar and the maximum supply pressure to the secondary circuit is 10.0 bar.
Max operating temperature 65°C.
- Section:
- 1465 Heaters
- Section Subtitle:
- Combination boilers and Water Jacketed Tube heaters. Low volume water content. Heat retained in water heaters will cause expansion of water after closure of draw-off taps and valves. Provision for expansion of water must be made to accommodate excess pressure within the system. Particular care is required where check valves are positioned, or loose jumper valves are thought to be upstream of the heater.
- WRAS Approval Number:
- 2207350
- Size:
- Secondary: 15mm compression.
Primary: 22mm compression.
- Marking:
- Ideal heating printed on front casing.
Model and size printed on drop down door.
- Installation Requirements:
- R001 R140 R360
- Expiry date:
- 31/07/2027
- Proviso:
- Supplied with a temporary filling loop. The filling loop must be installed with the appropriate backflow prevention device in accordance with clause G24.2, Guidance to the Water Supply (Water Fittings) Regulations 1999.
- Model:
-
Logic Max Combi² C24 – UIN 228334,
Logic Max Combi² C30 – UIN 228335,
Logic Max Combi² C35 – UIN 228336,
Logic + Combi² C24 – UIN 228329,
Logic + Combi² C30 – UIN 228330,
Logic + Combi² C35 – UIN 228331,
Logic Combi² C24 – UIN 228307,
Logic Combi² C30 – UIN 228308,
Logic Combi² C35 – UIN 228309.
- Approval Holder:
- Ideal Boilers
Company Name
Ideal Boilers
Address
PO Box 103
National Avenue
Kingston upon Hull
Postcode
HU5 4JN
Phone
+44 (0) 1482 492251
General Email
commercial_heating@idealheating.com
View All Listings by this Company - Manufacturer:
- Ideal Boilers
Company Name
Ideal Boilers
Address
PO Box 103
National Avenue
Kingston upon Hull
Postcode
HU5 4JN
Phone
+44 (0) 1482 492251
General Email
commercial_heating@idealheating.com
View All Listings by this Company