Section Code 5042 : Site applied pipe and fittings coatings. Compliance with BS6920 relates to the conditions of cure specified in the listing. If the cure conditions are varied from those described below then compliance with BS6920 cannot be assummed without further testing. Where catalysts are required, only tested catalysts in the recommended concentrations should be used. Manufacturer's advice must be sought if any non standard mixing or curing conditions are being considered.
Back To Directory Sections‘Nitocote EP405 (3821)’. Site applied, blue coloured, two component solvent free epoxy resin coating consisting of two bases (coat 1 base; Nitocote EP405 white & coat 2 base; Nitocote EP405 blue) & clear EP405 hardener. Mix parts A & B of each coat in a 100:13 weight ratio and apply in accordance with Fosroc data sheet issue 7 (CI/SfB: Pn6) dated November 2013. Cure coat 1 for 18 hours@7°C. Cure coat 2 for 21 days@7°C. For use with water up to 23°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mixing and/or curing conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
'Eucoflex Caliente'. Site applied, blue coloured, two-component polyurea coating consisting of Component A, Component B and Component C (Pigment Paste). Mix & apply as per manufacturers datasheet 'TX40T815', dated 'August 2023'. For use with water up to 60°C. This approval is valid only for the material when it is applied by experienced, suitably trained applicators that are authorized and/or certified by Euclid Chemical Toxement. The authorization, training and certification of the local applicators are the responsibility of Euclid Chemical Toxement and not the responsibility of WRAS.
'Geospray'. Site applied, grey coloured, geopolymer cementitious material. Mix 300g of powder with 60ml water and apply as per manufacturer's instructions 'V: 09.06.2022'. Cure for 96 hours@3°C. For use with water up to 23°C. This material is only approved for the mixing and curing conditions that appear on the approval. If the mix and/or cure conditions are varied from those specified on the approval then the material is not covered by the scope of the approval.
Page 9 of 9
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.