Section Code 2200 : Pressure reducing.
Back To Directory SectionsManually adjustable pressure reducing valve, which incorporates a DZR brass body and an in-line double check valve assembly on the inlet (verified by test as suitable for backflow protection against Fluid Category 3). The outlet incorporates a shut-off valve. Maximum supply pressure 16.0 bar. Maximum outlet pressure between 1.5 bar and 6.0 bar. Maximum operating temperature 40°C.
Range of 5 way inlet control group assembly incorporating a DZR brass body incorporating a pressure reducing valve, with an adjustable outlet pressure range of either 3.0 bar, 3.5 bar, or 6.0 bar and a safety relief valve set at either 6.0 bar or 8.0bar (depending on model). The product incorporates an inline single check valve cartridge after the balanced cold take off, verified by test (suitable for backflow protection against Fluid Category 2). Maximum supply pressure 10.0 bar. Maximum operating temperature 85°C
Range of adjustable pressure reducing (pilot) valves with stainless steel bodies, EPDM diaphragm and ‘O’-ring. Outlet pressures are adjustable between 1.0 to 5.0 bar (ACV100C model), 1.5 to 10.0 bar (ACV100E model) and 2.0 to 15.0 bar (ACV100F model). Maximum supply pressure 16.0 bar. Cold water use only.
In-line adjustable pressure reducing valve assembly with a DZR brass body. The assembly also incorporates a stainless strainer (part of the pressure reducing valve), a spherical valve with a brass ball on the inlet, a single check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2) on the outlet, and a drain port with a brass plug. The product also includes a port with a plastic plug to accommodate a gauge/sensor (not supplied). Adjustable outlet pressure range between 1.0 and 6.0 bar. Maximum supply pressure 10.0 bar. Maximum operating temperature 85°C.
Monobloc assembly with a DZR brass body comprising of a stainless steel strainer, adjustable pressure reducing valve and two approved check valve cartridges, however, the complete product has not been fully tested to demonstrate it provides backflow protection. The product is supplied with two loose pressure gauges. For use with copper pipe (manufactured to EN1057). The product is also supplied with Maximum inlet supply pressure 6.0 bar. Maximum outlet pressure 0.8 bar to 6.0 bar. Maximum operating temperature 35°C.
Page 5 of 15
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.