Range of indirect heat interface units with copper brazed stainless-steel heat exchangers, providing heating and instantaneous hot water.
The products incorporate an expansion vessel on the cold-water supply to the plate heat exchanger and a safety relief valve on the space heating circuit set @ 3.0 bar.
The domestic hot water and space heating circuit are both fitted with drain valves incorporating cover caps.
Maximum working pressures:
Domestic hot water 10.0 bar.
Space Heating 2.5 bar.
District Heating 3.0 bar.
Maximum operating temperature 85˚C.
- Section:
- 1350 Heat Exchangers
- WRAS Approval Number:
- 2011035
- Size:
- Domestic hot water and District heating circuits: ¾” BSP (M) inlet/outlet.
Space heating circuit: ¾” BSP captive nut inlet/outlet.
- Marking:
- YGHP on front cover.
YGHP, model number, company address and technical info on adhesive label on side of body.
- Installation Requirements:
- R001 R140 R360 R511
- Expiry date:
- 30/11/2025
- Proviso:
- Not supplied with a temporary filling loop. A filling loop must be installed with the appropriate backflow prevention device in accordance with clause G24.2, Guidance to the Water Supply (Water Fittings) Regulations 1999.
- Model:
-
YGINDRADSTD33/10.1 - YGHP INDIRECT STANDARD HIU (RADIATORS) - DHW 33kW / HTG 10kW.
YGINDRADSTD40/10.1 - YGHP INDIRECT STANDARD HIU (RADIATORS) - DHW 40kW / HTG 10kW.
YGINDRADSTD50/10.1 - YGHP INDIRECT STANDARD HIU (RADIATORS) - DHW 50kW / HTG 10kW.
YGINDRADSTD60/10.1 - YGHP INDIRECT STANDARD HIU (RADIATORS) - DHW 60kW / HTG 10kW.
YGINDRADSTD75/10.1 - YGHP INDIRECT STANDARD HIU (RADIATORS) - DHW 75kW / HTG 10kW.
YGINDRADSTD90/10.1 - YGHP INDIRECT STANDARD HIU (RADIATORS) - DHW 90kW / HTG 10kW.
YGINDRADSTD120/10.1 - YGHP INDIRECT STANDARD HIU (RADIATORS) - DHW 120kW / HTG 10kW.
Models added March 2021:
YGINDUFHSTD33/10.1 - YGHP INDIRECT STANDARD HIU (UFH) - DHW 33kW / HTG 10kW
YGINDUFHSTD40/10.1 - YGHP INDIRECT STANDARD HIU (UFH) - DHW 40kW / HTG 10kW
YGINDUFHSTD50/10.1 - YGHP INDIRECT STANDARD HIU (UFH) - DHW 50kW / HTG 10kW
YGINDUFHSTD60/10.1 - YGHP INDIRECT STANDARD HIU (UFH) - DHW 60kW / HTG 10kW
YGINDUFHSTD75/15.1 - YGHP INDIRECT STANDARD HIU (UFH) - DHW 75kW / HTG 15kW
YGINDUFHSTD90/15.1 - YGHP INDIRECT STANDARD HIU (UFH) - DHW 90kW / HTG 15kW
YGINDUFHSTD120/30.1 - YGHP INDIRECT STANDARD HIU (UFH) - DHW 120kW / HTG 30kW
Product Images
- Approval Holder:
- YGHP