Range of stainless steel indirect unvented hot water storage cylinders. The secondary circuit is factory fitted with a temperature and pressure relief valve (7.0 bar and 90°C). The product is fitted with a safety kit which comprises of a manifold, check valve cartridge, verified by test (suitable for backflow protection against Fluid Category 2) strainer, an expansion relief valve set at 6.0 bar and a pressure reducing valve set at 3.0 bar. A tundish and expansion vessel also comes supplied. Maximum working pressure: Secondary circuit: 5.5 Bar Primary circuit: 3.0 Bar Solar circuit: 3.0 Bar
Non-metallic materials and components comply with BS6920 at 80°C
Page of 1
We use cookies to give you the best possible experience with WRAS. Some are essential to provide website functions and ensure the website is secure. We also use cookies to help us understand how people use the site and to make improvements. Click "Accept All" to enable recommended settings or click "Manage cookies" to adjust your settings. For more details, see our Cookie Policy.